KLD-DVR Series

Dynamic Voltage Regulation Real-time Control Equipment

KLD-DVR Series Dynamic Voltage Regulation Real-time Control Equipment

It’s an off-line short duration energy compensation solution. When voltage dips and other issues occur, it can quickly support the load without power outage during switching to ensure the integrity of the supply voltage.

PRODUCT OVERVIEW

With the rapid development of the modern electric power industry and the transformation in the structure of electricity loads in the system, social production and precision manufacturing are growingly dependent on electronic equipment. Voltage dips have become a major problem for users.

According to the data of EPRI, more than 92% of power quality events are voltage dips and swells, while other power quality events only account for less than 8%. Voltage dips have been identified as the most prevalent event in power systems by a number of international research organizations. Therefore, it is vital to protect the sensitive equipment from voltage dips (swells). KLD-DVR series dynamic voltage regulation real-time control equipment provides the solution of voltage dips (swells) equipment, which can quickly correct the voltage in real time and solve the problem of voltage dips, swells and interruptions in the power supply of social production or precision manufacturing, ensuring that the loads continue to operate and the power supply will not be interrupted.

VOLTAGE DIP

The definition of voltage dips is specified in IEEE standard and national standards "Power quality—Voltage dips and short interruptions": a phenomenon that the effective power frequency voltage of a point in the power system is temporarily reduced to 10% ~ 90% of the rated voltage, and lasts for 10ms ~ 1min, during which the system frequency remains the nominal value and then returns to normal level.

OPERATION MODE INTRODUCTION

01 Grid voltage is in normal operation

KLD-DVR is in grid power supply mode, where the grid supplies power directly to the load through the equipment, while the KLD-DVR converter obtains energy from the output side to charge the supercapacitor.

02 When grid voltage dips(sags) or power failure occurs

KLD-DVR switches to inverter-fed mode. Energy stored in supercapacitors is converted into standard-quality voltage source by bidirectional converter to power the load.

03 After grid voltage recovers

DVR returns to grid-fed mode. The grid feeds the load directly. Meanwhile, the bidirectional converter draws energy from output side to recharge supercapacitors.

04 Fault Bypass Operation

If the static switch trips due to fault, the fault bypass switch will be closed immediately to guarantee uninterrupted normal power supply for loads.

05 Maintenance Bypass Operation

When KLD-DVR is under maintenance, load current is automatically transferred to the bypass switch, and the grid supplies power to the load directly.

HIGH-VOLTAGE DVR BRIEF INTRODUCTION

01 Grid voltage is in normal operation

KLD-DVR high-voltage DVR is an off-line series voltage compensation device for high-voltage distribution networks. It mitigates various transient-voltage disturbances including deep voltage dip(sag), swell and short-time voltage interruption.
Adopting low-voltage inversion plus step-up transformer topology, it is connected in series into 10 kV busbar via static switch. Supercapacitor energy storage provides voltage support with fully automatic operation. When bus voltage is normal, bypass conducts and the unit runs in low-power standby status. Upon detection of voltage abnormality, the control system triggers compensation within millisecond level. The inverter unit generates compensation voltage, which is superimposed onto busbar through step-up transformer to rapidly restore bus voltage to rated value with no manual intervention required.

FAST COMPENSATION EFFECT

KLD-DVR series can provide fast and accurate protection for the user's important equipment, preventing voltage dips and swells from causing equipment shutdown and economic losses. Even if the voltage drops to zero, the equipment can still output 100% of the rated voltage to support the normal operation. The typical response time is less than 2ms.

KLD-DVR Standard type

Input
Rated AC input line voltage200V-400V
Grid frequency range50Hz/60Hz±2.5Hz
Wiring mode3-phase 3-wire / 3-phase 4-wire
Efficiency>99%
Output
Compensation capability0~130% rated voltage (full-depth sag and swell coverage)
Short-time outage support time0~5s (supercapacitor capacity customizable)
Output frequency50±0.01Hz or 60±0.01Hz
Voltage compensation accuracy≤±1%
Voltage harmonics≤3%
Voltage unbalance (negative/positive sequence)<3% under 100% unbalanced load
Overload capability150%, for 10s
Performance
Voltage sag compensationYes
Voltage swell compensationYes
Manual mechanical bypassYes
Full response timeTypical <2ms
Noise≤60dB (100% load)
CoolingForced air cooling / natural air cooling
ProtectionShort circuit, DC bus under/over voltage, power semiconductor fault, overload protection, etc.
DisplayTouch screen display
CommunicationRS485, Ethernet, MODBUS protocol, remote monitoring supported
Operating Environment
Ambient temperature-25℃~+45℃
Ambient humidityMax. 95%RH (non-condensing)
Storage temperature-40℃~+70℃
Altitude≤2000m; derate 1% per additional 100m above 2000m
Ingress protectionIP54/IP20 (outdoor/indoor optional)

KLD-DVR High-voltage type

Input
Rated AC input line voltage10kV
Grid frequency range48.5Hz~51.5Hz
Wiring mode3-phase 3-wire
Efficiency>99%
Output
Compensation capability0~130% rated voltage (full-depth sag and swell coverage)
Short-time outage support time0~5s (supercapacitor capacity customizable)
Output frequency50±0.01Hz
Voltage compensation accuracy≤±1%
Voltage harmonics≤3%
Voltage unbalance (negative/positive sequence)<3% under 100% unbalanced load
Overload capability150%, for 10s
Performance
Voltage sag compensationYes
Voltage swell compensationYes
Manual mechanical bypassYes
Full response timeTypical <2ms
Noise≤60dB (100% load)
CoolingForced air cooling / natural air cooling
ProtectionShort circuit, DC bus under/over voltage, power semiconductor fault, overload protection, etc.
DisplayTouch screen display
CommunicationRS485, Ethernet, MODBUS protocol, remote monitoring supported
Operating Environment
Ambient temperature-25℃~+45℃
Ambient humidityMax. 95%RH (non-condensing)
Storage temperature-40℃~+70℃
Altitude≤2000m; derate 1% per additional 100m above 2000m
Ingress protectionIP54/IP20 (outdoor/indoor optional)

  • Input

    Rated AC input line-to-line voltage:200V-400V

    Grid frequency range:50/60±2.5Hz

    Wiring mode:Three-phase three-wire/Three-phase four-wire

    Operating efficiency:>99%

    Output

    Compensation capability:0~130% rated voltage (full-depth dip & swell coverage)

    OShort-time power-failure support duration:0~5s(supercapacitor capacity customizable)

    Output Frequency:50±0.01Hz or 60±0.01Hz

    Voltage compensation accuracy:≤±1%

    Voltage THD:≤3%

    Voltage unbalance(negative-sequence / positive-sequence):100% under 100% unbalanced-load condition

    Overload capacity:150% rating, 10 s duration

    Performance Index

    Voltage dip compensatione: Supported

    Voltage swell compensation: Supported

    Mechanical maintenance bypass: Supported

    Total response time: Typical value <2 ms

    Acoustic noisee: ≤60db(100% load)

    Cooling method: Forced-air cooling / natural-air cooling

    Protection functions: Short-circuit protection; DC-bus under-voltage / over-voltage protection; power-semiconductor fault protection; overload protection, etc.

    Human-machine interface: Large-size touch-screen display

    ACommunication: RS485, Ethernet, MODBUS protocol; remote monitoring supported

    Ambient Conditions

    Operating ambient temperature: -25℃~+45℃

    Relative humidity: Max.95%RH (non-condensing)

    Storage temperature: -40℃~+70℃

    Altitude: ≤2000 m; derate power by 1% per additional 100 m above 2000 m

    Ingress protection class: IP54/IP20 (outdoor / indoor optional)

  • Input

    Rated AC input line-to-line voltage:10kV

    Grid frequency range:48.5Hz~51.5Hz

    Wiring mode:Three-phase three-wire

    Operating efficiency:>99%

    Output

    Compensation capability:0~130% rated voltage (full-depth dip & swell coverage)

    OShort-time power-failure support duration:0~5s(supercapacitor capacity customizable)

    Output Frequency:50±0.01Hz

    Voltage compensation accuracy:≤±1%

    Voltage THD:≤3%

    Voltage unbalance(negative-sequence / positive-sequence):≤3% under 100% unbalanced-load condition

    Overload capacity:150% rating, 10 s duration

    Performance Index

    Voltage dip compensatione: Supported

    Voltage swell compensation: Supported

    Mechanical maintenance bypass: Supported

    Total response time: Typical value <2 ms

    Acoustic noisee: ≤60db(100% load)

    Cooling method: Forced-air cooling / natural-air cooling

    Protection functions: Short-circuit protection; DC-bus under-voltage / over-voltage protection; power-semiconductor fault protection; overload protection, etc.

    Human-machine interface: Large-size touch-screen display

    ACommunication: RS485, Ethernet, MODBUS protocol; remote monitoring supported

    Ambient Conditions

    Operating ambient temperature: -25℃~+45℃

    Relative humidity: Max.95%RH (non-condensing)

    Storage temperature: -40℃~+70℃

    Altitude: ≤2000 m; derate power by 1% per additional 100 m above 2000 m

    Ingress protection class: IP54/IP20 (outdoor / indoor optional)