KLD-FAE Series

Automatic Electrical Fire-extinguishing System

KLD-FAE Series Automatic Electrical Fire-extinguishing System

A new generation of wireless automatic electrical fire extinguishing system integrates "early warning, alarm and fire extinguishing", which is widely applied to power distribution cabinets in multiple scenarios.

PRODUCT OVERVIEW

In the power distribution system, most of the equipment are power distribution cabinets, network cabinets, cables and wires in cable tunnels or bridges. Due to the relatively closed space, the traditional fire alarm system focuses on the protection of the entire computer room or power distribution room. The fire can not be detected through video surveillance in the early stage, and the fire-extinguisng system will only started when the fire spreaded to a certain extent, but the equipment has already experienced serious damage. And there is no way to implement real-time monitoring and automatic fire extinguishing of confined spaces, thus can not control the source of the fire!

KLD-FAE series automatic electrical fire-extinguishing system integrates "early warning, alarm, extinguishing" functions, which has superior performance and high reliability, and it’s easy to install and maintain, meeting the urgent need of all users. It can be used independently or be networked with the control center.
The system rapidly monitors the changes in the surrounding environment through the installation of distributed remote sensing module. Once the fire is detected, the system will quickly send an alarm signal through wireless communication to inform the location and the time of occurrence of the fire. It can automatically extinguish the fire while remotely informing the fire situation to ensure that the fire can be extinguished the first time.

AUTOMATIC ELECTRICAL
FIRE-EXTINGUISHING SYSTEM

KLD-FAE series automatic electrical fire-extinguishing system is mainly composed of three main devices: automatic alarm and fire-extinguishing system host, automatic alarm and fire-extinguishing controller and automatic fire-extinguishing device. The host receives the online monitoring data from the automatic alarm and fire-extinguishing controller and displays the temperature and smoke detection status in real time through wireless transmission. When an electrical fire occurs, the controller can quickly control the automatic fire-extinguishing device to extinguish the fire.

SMS ALARM FUNCTION

The system configuration is flexible and convenient, and can be installed anywhere in the monitored cabinet that needs to extinguish the fire, It protects the system uninterruptedly in 24-hours and the User can remotely receive the early warning alarm SMS information.

SMS ALARM FUNCTION

The system configuration is flexible and convenient, and can be installed anywhere in the monitored cabinet that needs to extinguish the fire, It protects the system uninterruptedly in 24-hours and the User can remotely receive the early warning alarm SMS information.

COMPREHENSIVE PROTECTION FUNCTION

KLD-FAE series automatic electrical fire-extinguishing system is a complete electrical fire monitoring and control system that has the performance of abnormal warning, fire alarm, automatic fire extinguishing, system process display and fire protection record management.

SINGLE SERIES AUTOMATIC
FIRE-EXTINGUISHING EQUIPMENT

Single series automatic fire-extinguishing equipment has the ability to operate independently and does not depend on external equipment or system support, which not only simplifies the installation process, but also reduces the maintenance and management costs.

MATCHBOX SERIES AUTOMATIC
FIRE-EXTINGUISHING EQUIPMENT

Matchbox series follows a miniaturized design concept that aims to provide quick and efficient fire extinguishing, which can quickly respond to fire and automatically extinguish the fire. The products can easily be placed in narrow spaces such as communication cabinets, small power distribution boxes, drawers, etc., saving a lot of valuable spaces for users.

Technical Parameters

Automatic alarm and fire extinguishing system host KLD-FAE-MC
Input Power DC 12V(Adaptable to power AC220V input, DC12V output)
Operating frequency 50Hz/60Hz±5Hz
Communication RS232 or RS485, GSM(optional)
Wireless communication band Dual frequency GSM900MHz and DCS1800 MHz(Phase 2+)
Alarm mode 8 alarm phone numbers configurable
Display LCD touch display panel
Ambient temperature -40℃~+85℃
Environment Humidity Maximum 95%RH (no condensing)
Altitude ≤2000 meters (higher altitude can be customized)
Protection degree IP20(other requirements can be customized)
Automatic alarm fire-extinguishing controller KLD-FAE-CT
Input Power DC 12V
Operating frequency 50Hz/60Hz±5Hz
Detection accuracy ±0.5℃
Smoke sensitivity Compiles with UL-217 standard
Alarm mode Audible and visual alarm (optional)
Alarm intensity 85dB(10ft)
Ambient temperature -40℃~+125℃
Environment Humidity Maximum 95%RH (no condensing)
Altitude ≤2000 meters (higher altitude can be customized)
Protection degree IP20(other requirements can be customized)
Automatic fire extinguishing equipment KLD-FAE-ED
Operating voltage DC12V
Starting current 0.3A-1A
Protection space ≤3m³(others can be customized)
Release time ≤30s
Spray surface temperature ≤200℃
Thermal clearance 100mm at the nozzle≤75℃
Product insulation performance ≥20MΩ
Service life 10 years
Connection mode Multiple pcs in series
Ambient temperature -40℃~+125℃
Environment Humidity Maximum 95%RH (no condensing)
Altitude ≤2000 meters (higher altitude can be customized)
Protection degree IP20(other requirements can be customized)

S series automatic fire extinguishing equipment KLD-FAE-ED1S
Protection space ≤3m³(others can be customized)
Release time ≤30s
Spray surface temperature ≤200℃
Thermal clearance 100mm at the nozzle≤75℃
Product insulation performance ≥20MΩ
Service life 10 years
Ambient temperature -40℃~+125℃
Environment Humidity Maximum 95%RH (no condensing)
Altitude <1500 meters (higher altitude can be customized)
Protection degree IP20(other requirements can be customized)
Starting mode Thermal sensitive wire

M series automatic fire extinguishing equipment KLD-FAE-ED1M
Protection space ≤0.3m³(others can be customized)
Release time ≤5s
Spray surface temperature ≤200℃
Thermal clearance 100mm at the nozzle≤75℃
Product insulation performance ≥20MΩ
Service life 10 years
Ambient temperature -40℃~+125℃
Environment Humidity Maximum 95%RH (no condensing)
Altitude <1500 meters (higher altitude can be customized)
Protection degree IP20(other requirements can be customized)
Starting mode Thermal sensitive wire
Technical Parameters


Automatic Electrical Fire-extinguishing System

  • Input Power :DC 12V(Adaptable to power AC220V input, DC12V output)

    Operating frequency:50Hz/60Hz±5Hz

    Communication:RS232 or RS485, GSM(optional)

    Wireless communication band:Dual frequency GSM900MHz and DCS1800 MHz(Phase 2+)

    Alarm mode:8 alarm phone numbers configurable

    Display:LCD touch display panel

    Ambient temperature:-40℃~+85℃

    Environment Humidity:Maximum 95%RH (no condensing)

    Altitude:≤2000 meters (higher altitude can be customized)

    Protection degree:IP20(other requirements can be customized)

Automatic alarm fire-extinguishing controller

  • Input Power :DC 12V

    Operating frequency:50Hz/60Hz±5Hz

    Detection accuracy:±0.5℃

    Smoke sensitivity:Compiles with UL-217 standard

    Alarm mode:Audible and visual alarm (optional)

    Alarm intensity:85dB(10ft)

    Ambient temperature:-40℃~+125℃

    Environment Humidity:Maximum 95%RH (no condensing)

    Altitude:≤2000 meters (higher altitude can be customized)

    Protection degree:IP20(other requirements can be customized)

Automatic fire extinguishing equipment

  • Operating voltage:DC12V

    Starting current:0.3A-1A

    Protection space:≤3m³(others can be customized)

    Release time:≤30s

    Spray surface temperature:≤200℃

    Thermal clearance:100mm at the nozzle≤75℃

    Product insulation performance: ≥20MΩ

    Service life:10 years

    Connection mode:Multiple pcs in series

    Ambient temperature:-40℃~+125℃

    Environment Humidity:Maximum 95%RH (no condensing)

    Altitude:≤2000 meters (higher altitude can be customized)

    Protection degree:IP20(other requirements can be customized)

S series automatic fire extinguishing equipment

  • Protection space:≤3m³(others can be customized)

    Release time:≤30s

    Spray surface temperature:≤200℃

    Thermal clearance:100mm at the nozzle≤75℃

    Product insulation performance: ≥20MΩ

    Service life:10 years

    Ambient temperature:-40℃~+125℃

    Environment Humidity:Maximum 95%RH (no condensing)

    Altitude:<1500 meters (higher altitude can be customized)

    Protection degree:IP20(other requirements can be customized)

    Starting mode:Thermal sensitive wire

M series automatic fire extinguishing equipment

  • Protection space:≤0.3m³(others can be customized)

    Release time:≤5s

    Spray surface temperature:≤200℃

    Thermal clearance:100mm at the nozzle≤75℃

    Product insulation performance: ≥20MΩ

    Service life:10 years

    Ambient temperature:-40℃~+125℃

    Environment Humidity:Maximum 95%RH (no condensing)

    Altitude:<1500 meters (higher altitude can be customized)

    Protection degree:IP20(other requirements can be customized)